Once you have turned your inverter on the screen will show the below options which have to be set before you can proceed:
Settings on start up #
1. Safety:
- Press ✔, and scroll ⬇ to NRS_SA,
- Press ✔, the screen will ask to Set Safety,
- Press ✔, the screen will display Success.
- Press ↩, to get back to the settings screen.
2. Date & Time:
- Press ✔, set current date & time,
- Press ✔, the screen will ask to Set Date & Time,
- Press ✔, the screen will display Success.
If done correctly your inverter will say it is in OFF Mode, this is correct.
Please follow the below steps:
- Open the settings menu by pressing ✔ on the home screen,
- then scroll ⬇ to Settings and press ✔.
- The factory password will be: 0000
Setting the inverter preferences #
1: On Grid
- Scroll ⬇ to On-Grid, press ✔
- Scroll ⬇ to Export Control, press ✔
- Set to 0000W, press ✔
(can be adjusted remotely) - Screen will ask to *Set Parameter*, press ✔
- Screen will display *Success*
- Press ↩
- Press ↩again
2: Off-Grid
- Scroll ⬇ to Off-Grid, press ✔
- Scroll ⬇ to EPS Output, press ✔
- Scroll ⬇ to Enable, press ✔
- Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩
Press and hold the ✔ button for 2 seconds.
The screen will display *START?*.
Press ✔ to set, and the inverter will start up.
3: UPS Output
- Scroll ⬇ to UPS Output, press ✔
- Scroll ⬇ to Enable, press ✔
- Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩
- Press ↩again
4: Battery
- Scroll ⬇ to Battery, press ✔
- Scroll ⬇ to Min-SOC, press ✔
- Set to 10%, press ✔
- Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩
5: On Grid Min SOC
- Scroll ⬇ to OnGrid Min SOC, press ✔
*Set to clients requirements – If system is being used as a back-up only system, the recommended setting would be 100% - Press ✔
- Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩
- Press ↩again
6: Feature
- Scroll ⬇ to Feature, press ✔
- Scroll ⬇ to Meter/CT, press ✔
- Scroll ⬇ to SET, press ✔
- Scroll ⬇ to CT, press ✔
(*When installing a Meter, set accordingly) - Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩
7: Bypass Relay
- Scroll ⬇ to Bypass Relay, press ✔
- Scroll ⬇ to Internal, press ✔
(*If not set, the inverter will not operate in EPS) - Screen will ask to Set Parameter, press ✔
- Screen will display Success
- Press ↩ repeatedly until you see the home screen
Press and hold the ✔ button for 2 seconds.
The screen will display *START?*
Press ✔ to set, and the inverter will start up.